M-Bus level converter MPW6 with serial interface

With the M-Bus level converters from the MPW-IP series from STV Electronic, you can easily, safely and efficiently connect your controller, such as the Smart Manager 4.0 for energy data acquisition and control, to your M-Bus network.

Our level converters connect the meter data from your sensors and also the control of your actuators in the M-Bus network via the Ethernet interface.

The parameterization and monitoring takes place via the integrated website. If desired, this can be protected against unauthorized changes with a password.

The IP level converters from STV offer you a great advantage: They constantly display the M-Bus voltage and current on the integrated website. In this way, the M-Bus networks can be monitored quickly and easily.

for up to 6 M-Bus standard loads

 

 

Zusätzliche Informationen

Gewicht n. v.
Größe 3 × 9 × 5 cm
Power supply

24 Vdc +/- 20%, 24 Vac +/- 5%

Internal consumption

RS: 60 mA at 24Vdc, IP: 85 mA at 24 Vdc

Protection

IP20

Operating temperature

min. 0 – 50°C

M-Bus voltage

37 V

M-Bus current

RS: 9 mA (up to 6 standard loads à 1,5 mA ), IP: 24 mA (16 standard loads à 1,5 mA)

Over-current threshold

>30 mA

Interfaces

RS-485, RS-232